Publication 1757-RN508A-EN-P - October 2003
12 ProcessLogix R500.1 Service Pack 1
39099 Backup Utility The utility creates points.bak on backup but doesn't appear to
rename points.bak to points on a restore
After a restore copy points.bak to
points while the database service is
stopped.
34574 Batch Reporting Server wide report configuration settings don't apply to batch
reports
35827 Batch Reporting With every new batch report, a shortcut is created in C:\, pointing to
the report's .xls file.
42165 Conf. Daemon
(confd)
Pntbld can be left running if a download is attempted during server
shutdown
34513 Display Pages Point Browser does not remain visible after use on a trend display Press the Point Browser activation
button again
35636 Display Pages Fast history interval maybe shown incorrectly as 5 seconds in drop
down list when another fast history period is selected during
installation
Navigate to the System Acronym
pages (sys154) and change
acronym number 186 to x sec,
where x is the sample period for
Fast History.
36642 Display Pages On a fresh install the pop up help on page sysMnuConfiguration.dsp
are unreadable.
Install the Arial Narrow font.
34215 Display
Subsystem
Trend hairline cursor can display incorrectly when chart has a large
timescale buffered
35270 Display
Subsystem
Detail display callup behavior (via double click) is inconsistent when
the area is not assigned to the station
Single click DFD and perform a
detail (F12).
36384
1-8XB84
Display
Subsystem
After failover with trends up the plots may not appear Reload the page.
36890
1-98IBH
Display
Subsystem
1 second trends may show gaps if points are not configured in
history
35744 Event Archiving Operator and station fields are for archive, restore and removal of
events
35884 Event Archiving Appending on the tape using NTBACKUP sometimes does not work Do not perform appends to tape.
43202 Event Archiving Next archive date can be set incorrectly when enabling event
archiving
34358 Excel Data
Exchange
VB run-time error when retrieving more values than possible width
of a spreadsheet
Don't specify more cells than are
available to be filled.
35975 FSC Serial FSC Serial time synching does not work Use a method of synching the time
other than the FSC Serial scantask.
32136 Installation Installation may fail if password policy for Windows 2000 doesn't
allow password length of at least that which will be entered during
installation of ProcessLogix
Ensure that the length of
passwords is at least that of the
current policy.
34392 Installation Ability to change password of default mngr operator account can
render system unusable
Don't change the "mngr" operator's
password if it's linked to a
Windows user account via "Use
Windows account".
Table 4 Known Station Problems in R500.1 SP1
ISR Subsystem Description Workaround