Security Command R500 Especificaciones Pagina 154

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 584
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 153
8 – Configuring Points
136 R400
AlarmType8 The type of alarm 8, for example,
PVHI
25
✔✔
RollOver Accumulator input rollover value,
for example, a 12 bit counter rolls
over at 4095.
26
✔
MeterFactor The accumulator meter factor.
Normally 1.0, is adjusted after meter
proving.
27
✔
ScaleFactor The accumulator scale factor, for
example, 1 pulse.count = 5.678
liters.
28
✔
RawPV The value of the accumulator raw
input (the counter it is reading).
29
✔
SetpointLowLimit Data entry of Setpoint values below
this value will be rejected.
32
✔
SetpointHighLimit Data entry of Setpoint values above
this value will be rejected.
33
✔
OutputLowLimit Data entry of Outpoint values
below this value will be rejected.
34
✔
OutputHighLimit Data entry of Outpoint values
above this value will be rejected.
34
✔
LastProcessedDate The day when the value of the PV
last changed.
38
✔✔
✔
LastProcessedTime The time of day when the value of
the PV last changed.
39
✔✔
✔
H1M History Standard 1 min 41
✔✔✔
H6M History Standard 6 min 42
✔✔✔
H1H History Standard 1 hour 43
✔✔✔
H8H History Standard 8 hour 44
✔✔✔
H24H History Standard 24 hour 45
✔✔✔
H5SF History Fast 5 second. Configurable
between 1 and 30 seconds.
46
✔✔✔
H1HE History Extended 1 hour 47
✔✔✔
Internal Parameter Description
ID
Status
Analog
Acc.
Table 8.2 Internal Point Parameters
plscpcg.book Page 136 Monday, May 28, 2001 10:11 AM
Vista de pagina 153
1 2 ... 149 150 151 152 153 154 155 156 157 158 159 ... 583 584

Comentarios a estos manuales

Sin comentarios